|
Restaurant and Commercial
Kitchen Exhaust Hoods
|
|

|
"We Can Offer You a Complete and Affordable Solution to Kitchen Grease,
Smoke and Odors Generated From Residential or Restaurant Cooking..."
Without an effective kitchen exhaust hood cleaning system,
cooking grease and smoke causes grit and grime build-up on almost
every structure these emissions come into contact with... that can
cost you a lot of money in cleaning, maintenance and damage.
|
|
General Information... |
|
Introduction |
|
The science of commercial kitchen
ventilation includes both exhausting air as well as providing
replacement air within the cooking area. Whether a restaurant is
a small free-standing site or a large institutional kitchen,
managing and balancing airflow is a complex issue. It is a
challenge to properly ventilate commercial kitchens, as they
require moving large volumes of air through ductwork and
equipment placement in very restricted spaces.
Overall design, construction, installation coordination, and
maintenance are required to get optimum performance and an
energy-efficient air balance from the system.
SMACNA, through its technical manuals, provides the information
and drawings to illustrate the elements of construction and
installation of commercial kitchen exhaust hoods. The
information is intended to encourage standardization in
installations and to call attention to the appropriate
segregation of responsibilities of those involved with food
service design and installation.
|
|
A Typical
System |
|
A typical
kitchen ventilation system includes an exhaust hood or canopy,
ductwork, fan system, and a means of providing adequate make-up
air. The entire system must constitute a fire-safe assembly
within the building.
Exhaust hoods and canopies capture heat and contaminates in the
air by means of filters, extraction baffles (cartridges), and
water mist systems. There are many style variations of hoods
with canopy styles—a large box with and open bottom—being the
most common. Styles selection is based on the type of oven and
the expected contaminates to be removed. While there are several
styles of hoods, all fall within two major categories:
-
Type I hoods carry a listing label and are manufactured and
installed according to the manufacturer's and listing agencies'
requirements. They are designed to handle grease and include a
number of integrated components within the hood.
-
Type II hoods are used in the collection of steam, vapor, heat,
and odors—but not grease. The two sub-classifications of Type II
hoods are condensate and heat/fume.
Exhaust ductwork provides the means to transfer contaminated
air, cooking heat and grease vapors from the hood to the fan.
-
Ducts accumulate combustible grease and should be constructed
from 16- steel or 18-gage stainless steel as per code
requirements.
-
The ducts must me securely supported by non-combustible duct
bracing and supports designed to carry the gravity and seismic
loads as per code requirements, no fasteners should penetrate
the duct.
-
The duct is often run inside a shaft enclosure and that
enclosure is typically constructed of gypsum board, plaster,
concrete, or ceramic tiles and must be an approved continuous
fire-rated enclosure.
Exhaust fans move the heat and contaminated air out of the
building. All exhaust fan components must be accessible or have
removable access panels for cleaning and inspection and must be
designed to contain and drain any excess grease. There are three
major types of exhaust fans:
-
Up-blast fans are typically aluminum centrifugals that are
designed for roof mounting directly on top of the exhaust stack.
-
Utility fans are normally roof-mounted with the inlet and outlet
90 degrees from each other and are typically used where
high-static pressure losses exist.
-
Inline fans are typically located in the interior duct and are
used where exterior fan mounting is impractical.
In order for the exhaust system to work properly, make-up air is
required to replace air equal to the amount removed. Make-up air
can be provided via an independent system or in combination with
the building's HVAC system.
|
|
Kitchen Ventilation Concepts |
|
To better understand why a
restaurant kitchen exhaust hood needs to
be designed and constructed in a very specific manner, the
principles behind air movement must be understood. Buildings are
required to adhere to indoor air quality regulations and,
depending upon the jurisdiction, sometimes exhaust air quality
regulations. The food service industry must meet higher air
quality regulations than standard building exhausts due to the
type of contaminated air produced by cooking food.
Exhaust Air
Exhaust air is the starting point in restaurant kitchen
ventilation design. Exhaust air is the air that is contaminated
by smoke and grease-laden vapor (aerosols) created by the
cooking source. This air must be removed from the building in a
manner that complies with local codes and ordinances.
Replacement Air
Make-up or, supply air must be provided in approximately equal
amounts to replace the kitchen air being exhausted. Typically,
outside air is supplied through a designed make-up air system.
Most health codes require that an amount of fresh outside air be
included in any replacement air calculation to assist in indoor
air quality requirements.
|
|
The Kitchen Ventilation Team |
|
The safety and design requirements of both commercial kitchen
exhaust and make-up air systems require that a group of key
players have sufficient knowledge of the subject to coordinate
the entire process from design to operation. The following
overview provides a brief description of each team member with a
vested interest in the process and suggests criteria necessary
to design and install a comprehensive and balanced system that
offers efficient operating costs, climatic controls, and
satisfies building and fire regulations.
Owner/Facility Manager
An owner/facility manager needs to understand the
interdependence of each piece of the kitchen system to recognize
the value of having a complete and properly integrated system
that will provide a productive and comfortable work environment
that is also cost effective.
Architect
The architect is responsible for the commercial restaurant's
design including fire-resistive walls, floor-to-ceiling
assemblies, roof-ceiling assemblies, and the protection of
openings as well as the horizontal and vertical smoke barriers.
In consideration for fire protection, the architects first must
determine the overall function of the structure and the type of
occupancy of its spaces. The architect is also responsible to
design appropriate spaces within the building that are required
to be separated by fire-resistive assemblies with protected
openings, as set forth in the local building code. The architect
will communicate and cooperate with the authority having
jurisdiction at the building site and comply with any special
conditions of fire protection design required by that authority.
Contractors
Contractors must have access to and be able to use manuals and
design procedures in order to fully comply with design
objectives and specifications established by the kitchen
ventilation system designer. SMACNA's Kitchen Ventilation
Systems & Food Service Equipment Guidelines documents
industry-accepted practices for the fabrication and installation
of food service-related equipment.
Code Officials
Local code authorities must be capable of judging adequacy and
comparability in the installation of commercial kitchen
ventilation systems and its components and assemblies. The most
critical aspects of a code official's job are fire and safety
issues. However, understanding the "standards of practice" that
quality contractors strive to achieve is also important.
Engineer/System Designer
The engineer or system designer is responsible for knowing where
ducts, pipes, and other conduits pass through required
fire-rated separations or smoke barriers. Duct penetrations must
be shown on the mechanical plans and designed with an
appropriate protection method. Use of standard symbols is highly
recommended. International Mechanical Code (IMC) and the
National Fire Protection Association Standard # 96 Standard for
Ventilation Control and Fire Protection of Commercial Cooking
Operations (NFPA #96), NFPA 17A and 90A, all state that the
designer must show on the plans the location and mounting
details of all automatic fire doors, dampers, access panels, and
other fire protection means incorporated into both the exhaust
and supply systems.
To coordinate all requirements, designers must possess all
necessary information on barrier locations, occupancy
assignments, protection planning, rating, and identification of
compartments and structural components. Drawings must show fire
and smoke dampers and heat stops. The engineer/designer should
specify the hourly rating and type of damper and requirements
for access doors. Specific framing requirements of openings
should be provided in the architectural and structural drawings
submitted for building permits. Thickness and type of fire
resistive material may vary by jurisdiction. There should be
coordination in advance with local authorities to verify the
acceptance of the methods and equipment proposed for use.
|
|
Relevant
Codes and Standards |
|
Local codes are generally adopted from either the International
Mechanical Code (IMC) or the National Fire Protection
Association Standard # 96 Standard for Ventilation Control and
Fire Protection of Commercial Cooking Operations (NFPA #96) or a
combination of the two with particular local issues of concern
included. In many major cities, local codes are written and
published by local building officials; however, such codes are
frequently based on one of the national codes previously
mentioned.
Certain government agencies such as the General Services
Administration (GSA); the Department of Health and Human
Services (HHS); Housing and Urban Development (HUD); and the
U.S. Army Corps of Engineers have specific standards or codes
that must be accommodated in construction performed for these
agencies.
In some instances, the insurance companies that underwrite the
building have recommendations or standards from the American
Insurance Association (AIA).
Planners and designers need to identify and consult the local
authority having jurisdiction and local governing codes prior to
designing a kitchen ventilation system. Consideration must be
given to both the building and fire codes.
|
|
Cleaning
of Exhaust Systems |
|
In
accordance with Section 11.4 of the Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations (NFPA
Standard 96):
When to Clean? Who to Clean?
"Upon inspection, if found to be contaminated with deposits from
grease-laden vapors, the entire exhaust system shall be cleaned
by a properly trained, qualified, and certified company or
person(s) acceptable to the authority having jurisdiction in
accordance with Section 11.3.
What to Clean? How Clean is "Clean"?
"Hoods, grease removal devices, fans, ducts, and other
appurtenances shall be cleaned to bare metal prior to surfaces
becoming heavily contaminated with grease or oily sludge."
|
|
Inspection of Exhaust Systems |
|
In
accordance with Section 11.3 of the Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations (NFPA
Standard 96):
When to Inspect? Who to Inspect?
"The entire exhaust system shall be inspected by a properly
trained, qualified, and certified company or person(s)
acceptable to the authority having jurisdiction in accordance
with Table 11.3."
Table 11.3
Exhaust System Inspection Schedule
|
Type
or Volume of Cooking Frequency |
Frequency |
|
Systems serving solid fuel cooking operations |
Monthly |
Systems serving high-volume cooking operations
- such as 24-hour cooking, charbroiling, or wok cooking |
Quarterly |
|
Systems serving moderate-volume cooking operations |
Semiannually |
Systems serving low-volume cooking operations
- such as churches, day camps, seasonal businesses, or
senior centers |
Annually |
|
|
Kitchen
Hood Performance |
|
KANSAS CITY,
Mo. -- The position of appliances in a restaurant certainly
doesn't figure into the dining plans of most customers.
But new research into the impact of diversity of equipment and
its position on the performance of commercial kitchen hoods will
result in cost savings and better operating kitchens, both of
which may benefit customers.
Commercial kitchens typically use exhaust hoods to remove
effluents, such as smoke, grease and moisture, generated by
cooking operations.
To provide optimum energy efficiency, it is desirable to operate
with the minimum exhaust flow needed to provide sufficient
capture and containment of effluents. Higher exhaust usually
leads to higher HVAC loads to condition replacement air.
Research comparing the impact of the position of a single
appliance vs. multiple appliances under hoods on the minimum
exhaust airflow required will be conducted by ASHRAE.
"The research will help manufacturers and installers of HVAC and
kitchen ventilation equipment implement systems that are more
cost competitive and provide cost savings for their customers,"
Richard Swierczyna, a principal investigator of the project,
said. "Restaurant designers and consulting engineers will
benefit by gaining a better knowledge of kitchen ventilation
systems, which will help in providing better operating kitchens
for their customers."
ASHRAE approved funding totaling $986,953 for eight research
projects in the areas of indoor air quality, comfort and health,
energy conservation, operating and maintenance tools,
environmentally safe materials and design tools at its 2003
Annual Meeting held June 28-July 2.
Among them is 1202-TRP, Effect on Commercial Kitchen Hood
Performance of Appliance Diversity and Position. The principal
investigators are Swierczyna, Architectural Energy Corp.,
Boulder, Colo., and Donald Fisher, P.Eng., Fisher-Nickel Inc.,
San Ramon, Calif. The project is expected to take a year to
complete at a cost of $105,033. It is sponsored by ASHRAE
Technical Committee 5.10, Kitchen Ventilation.
The research will build on existing capture and containment
studies from single appliance operations to multiple appliances
underneath hoods. It also will examine how appliance positions
underneath hoods may impact required capture and containment
airflows.
"If ventilation manufacturers, kitchen designers and consulting
engineers knew that they could specify operation of hoods with
multiple appliances at lower flow rates, operations might
benefit from lower energy costs while also realizing improved
performance -- less heat gain and greater personnel comfort,"
Swierczyna said. "End-users would see these savings in the form
of both lower first and operating costs over the lifetimes of
equipment. The comfort issue also has economic consequences in
terms of personnel performance and turnover costs."
Results of the study may be incorporated into codes, standards
and design guides to assist code officials, commercial kitchen
and building designers, consulting engineers and ventilation
manufacturers with efficient restaurant design and operation.
Judi Dunlop,
09/03/2003,
www.ashrae.org
|
|
About
Cleaning |
|
Kitchen
exhaust cleaning is required by law for virtually every
commercial cooking establishment in the United States.
Restaurants, hospitals, hotels, employee cafeterias and other
food-service locations have a "hood" and ductwork over the stove
to exhaust smoke, steam, and fumes out of the building. These
exhaust gases leave a residue on the inside of the ductwork.
This is usually a grease residue of some sort, depending on the
type of cooking. Char broilers commonly leave heavy black
grease. Chinese cooking normally deposits a sticky or rubbery
residue. When a charcoal or wood-burning stove is in use soot
and ash residue builds up in the ductwork. Dishwashers leave
heavy lint deposits.
When the buildup of grease becomes heavy, a fire hazard exists.
Approximately one of three restaurant fires is caused by grease.
A common scenario of how a kitchen exhaust fire starts is this:
A flame flares up on the stove.
The fire contacts the filters above the stove on the kitchen
hood. The filters ignite.
Since the exhaust fan is on, drawing air into the hood, through
the filters, and up the duct, the flame on the filters is pulled
into the duct.
If significant grease residue exists on the duct interior, this
can act as a fuel and the fire spreads up the duct, perhaps all
the way into the fan. We have seen fire climb up a ten-story
duct to the fan on the roof and burn up the fan.
Modern duct construction is designed to hopefully withstand such
duct fires. The duct seams are welded to prevent grease or fire
from leaking out and the shafts around the duct are made of
fire- resistive materials. However, older buildings are still at
risk, and even in modern ones the fire may leak out or could
come out onto the roof via the fan.
When an exhaust system is cleaned regularly, however, the
chances of a duct fire are extremely remote.
METHODS OF CLEANING
There are two primary methods of cleaning kitchen exhaust
ductwork:
Scraping.
Pressure washing or steam cleaning.
The primary method used is scraping. This is the more economical
method and is extremely effective when done thoroughly. We know
of no duct fires that have occurred because of using this method
(unless it was done poorly). Scraping of duct systems complies
with the Uniform Fire Code that is the governing fire code of
the state of Washington. The cleaning method for kitchen
exhausts most often used by Commercial Vent Vac is the scraping
method.
The alternative to scraping is pressure washing or steam
cleaning. This is a more costly and time-consuming technique,
since it requires considerable prep work to control wastewater
and more expensive equipment is involved. However, this method
will clean ductwork down to "bare metal," which is the
recommendation of the National Fire Protection Association (NFPA)
as spelled out in NFPA Standard 96.
At Commercial Vent Vac, we frequently do pressure washing of
kitchen exhausts as well as scraping. This is done for a variety
of reasons. Sometimes the ductwork may be inaccessible for
scraping or the client simply wants to take the extra
precautionary step of having it cleaned to "bare metal."
HOW OFTEN SHOULD A KITCHEN EXHAUST BE CLEANED?
The most common cleaning frequency is every 3 months. This can
vary, however. The kitchen exhaust systems that need cleaning
most often are those over wood-burning or charcoal-burning
stoves. These should be cleaned every month at least, and in
some cases as often as every 2 weeks.
Below are various types of cooking establishments and their most
commonly recommended cleaning frequencies.
Wood-burning or charcoal-burning stoves, charbroilers, 24-hour
restaurants, and some hamburger places: 30 DAYS.
Many hamburger restaurants and fast-food locations: 60 DAYS.
Average restaurant, employee cafeteria, and hotel or hospital
kitchen: 90 DAYS.
Pizza places, convalescent hospital, small snack bar, oven hood:
180 DAYS.
Hoods over non-grease-creating appliances, such as steam
kettles, dishwashers, soup vats, etc. ONE YEAR.
Kitchen exhaust cleaning is a standard part of the routine
maintenance of any cooking establishment. All kitchen managers
and restaurant owners should be aware of its role in fire
prevention and ensure it is done on a regular basis.
|
|
Related Links

All Kitchen Exhaust Hoods |
BPA Air Quality Solutions is the
leader in providing you with the best choice of kitchen exhaust
hoods with integrated cooking ventilation filtration systems that will solve your problems
caused by smoke, grease and odors generated by your
restaurant cooking.
Our kitchen exhaust hoods emissions elimination systems installed in
your restaurant or home...
1. Eliminates cooking odors
There are different odor control technologies used in the
various kitchen exhaust hood systems. Let BPA Air Quality Solutions'
100+ years of combined air purification experience match you up with
the perfect kitchen emission system for your specific needs.
2. Saves you money
Without an effective kitchen exhaust hood cleaning system,
cooking grease and smoke causes grit and grime build-up on almost
every structure these emissions come into contact with... that can
cost you a lot of money in cleaning, maintenance and damage.
3. Keeps you in compliance
(for restaurant and commercial applications)
A restaurant and commercial kitchen exhaust hood cleaning system
will keep you within compliance with even the most strict federal,
state or local environmental standards. Installing the correct
commercial kitchen emission system for your needs the first time
around eliminates the need for costly retrofits later on down the
road.
|

Commercial Kitchen Exhaust
Hoods |

Commercial Kitchen Exhaust
Fans |

Kitchen Emissions Cleaning
Systems |
See our
entire line of commercial kitchen
emissions systems.
If you have
any questions, call us, we'll be glad to help!
1-877-688-2703
Return Policy |
Contact
Us | About Us | View
Cart | Check
Out
©2001 - 2006 - BPA Air Quality Solutions
LLC
(DBA BreathePureAir.com) is for educational and research intentions only and
is not intended as an alternative for medical treatment or advice. Use of
this website, the 90 day return policy, and free shipping is subject to our
published
privacy policy,
terms of service,
and return policy.
|
|