|
OPERATION & SERVICE - FOR THE MAINTENANCE ENGINEER
also see
Troubleshooting for ATS
|
WARNING! |
|
RISK OF ELECTRIC SHOCK
These service instructions are for
use by qualified personnel only. To reduce the risk of
electric shock, do not perform any servicing other than that
contained in the operating instructions unless you are qualified
to do so. |
1.Description and Principles of Operation
The basic ATS units are made up of five modular sections.
Each of the first three sections employs different mechanisms to remove and
capture particulate matter from the air.
The first section, an impinger, is primarily designed for, and is especially
effective in, capturing relatively large greasy liquid particulate. The
impinger is constructed of two equally spaced layers of roll formed baffles.
The spacing creates an air flow pattern which causes the contaminate to
collect and flow down the baffles. Holes in the frame permit the liquid to
drip into the drain basin below. Periodically, at a predetermined setting, a
remotely located control automatically activates oscillating wash manifolds
located on both sides of the impinger to flush away any remaining tenacious
matter. (Refer to the electronic air cleaner section below for addition
description on the integral washer. It is identical to the impinger washer.)
The second section houses an electronic air cleaner, technically known as an
electrostatic precipitator. In this type of equipment, all airborne
particles, even of microscopic size, are electrically charged (positively)
as they pass through a high voltage ionizer. These charged particles are
then attracted and adhere to a series of parallel collecting plates, which
form the negative elements of an electrostatic field.
The ionizing-collecting cells (contaminate collecting elements) are housed
in the cabinet on slide rails. They can be removed from the cabinet as
required, through the end access door, by sliding them out like drawers. On
multicell units, all of the electrical connections between cells in a given
tier are automatically made through spring connectors. On the access end,
the high voltage from the power packs is made with cables. When installing
cells into the cabinet, observe the directional arrows on the cell end
plates. The side of the cell containing the spiked ionizer blades always
must be locked on the air entering side.
The power supplies convert the 115 volt 60 Hz single phase AC supply to the
high voltage DC needed to power the cells. The power supplies are solid
state, pulse width modulated (PWM), line and load regulated. Potential
output voltages of 12.5 KVDC are required for the ionizer and 6.25 KVDC for
the collector at a maximum current of 6 MA. Each supply is retained in the
control in slide channels and secured with one bolt located in the top
corner of the circuit board.
At a predetermined frequency the remotely located control automatically
activates an integral wash system to flush away the collected contaminant.
When activated, the duration of the washing cycle is approximately 80
minutes.
In addition to the preset automatic wash cycle, the washing operation may be
initiated manually when required. The events in a wash cycle are:
a. Power packs and system blower “off”
b. Washer and detergent “on” (each module)
c. Washer and detergent “off” (each module)
d. Pause for detergent to react
e. Washer “on” for rinse (each module)
f. Washer “off” (each module)
g. Blower “on” for forced dry
h. Power packs “on”
When a fire control system is specified, both the impinger and electronic
air cleaner sections contain chemical spray nozzles.
The third section houses a bag filter(s). In the event of an electrical
outage in the electronic air cleaner, the bag filter acts as a safety backup
collector.
Also, in some applications, the bag filter will collect any precipitated
agglomerates that may tend to “blow-off” the electronic air cleaner.
When the bags become saturated with contaminant, they must be removed and
replaced. However, this requirement is relatively infrequent due to the
pre-filtration upstream from the bag.
A series of long deep pockets arranged side by side form the configuration
of each bag. The ultra fine fibers used in the makeup of the filtering media
offer to trap the contaminant.
The fourth section is employed in the ATS unit for odor control. Panels
filled with activated carbon granules are arranged in a vee bank
configuration to provide adequate surface area. The surface of each granule
is extremely porous and absorbs materials that are in a gaseous or vaporized
state that cannot be removed by the particulate filters. Using the carbon
filters without the pre-filtration by the bag filters is not recommended.
When the panels have become saturated or fully loaded they may be replaced
with new or reactivated carbon.
The fifth section, the blower/motor section, has been rated to handle the
air movement requirements for the systems and the adjoining ducting.
When the fire suppression system has been specified to be factory furnished
it consists of strategically located chemical spray nozzles located in the
impinger and electronic air cleaner modules. The fire suppression chemical
is stored in a cylinder housed in a weatherproof enclosure mounted on one
side of the blower module. An electrical detection device, mounted down
stream from the impinger module in the electronic air cleaner module,
activates the system by sending a signal to a control head discharging the
chemical cylinder.
In addition to the electrical detection device, a remotely located pull
station is provided for mechanical activation of the system manually.
Depending on the installation and any local, or other governing
requirements, the ATS unit fire suppression system may be tied in with other
fire suppression devices. When the fire suppression system is activated the
unit electrical input power is disconnected to the ATS unit blower and the
high voltage required for the electric air cleaner is disconnected. After
the fire suppression system has been activated, the authorized fire
suppression contractor must put it back into service. For a system supplied
with the ATS unit see
fig 7.
2. Initial
Start-Up
Prior to equipment start up, the fire extinguishing
system employed in the ATS unit (and possibly adjoining equipment) must be
inspected by properly trained and qualified personnel. This includes all
actuation components including remote manual pull stations, mechanical or
electrical devices, detectors, fire-actuated dampers, etc. These items shall
be checked for proper operation during the inspection in accordance with the
manufactures listed procedures. In addition to these requirements, the
specific inspection requirements of the applicable NFPA standard shall also
be followed. If required, certificates of inspection shall be forwarded to
the authority having jurisdiction. For a fire suppression system supplied
with the ATS unit see
fig 7.
A. Inspect the inside of the adjoining ductwork and Trion cabinet to
be sure it is clean and free of any debris or construction materials.
Especially note the opening in the drain basin for any restrictions. The
ducting, where secured to the cabinet collars, should be sealed watertight
with either gasketing or caulking.
B. Inspect the ionizing collecting cells to see that all of the
ionizing blades are intact and that no large pieces of foreign material are
lodged between the plates. Also, verify that the cells are properly
installed in the cabinet with the spiked ionizing blades located on the air
entering side (follow the air flow directional arrows)
C. Check the high voltage leads to see that they are connected to the
proper terminals, both at the ionizing-collecting cells and inside the power
pack. See fig 6
D. Be sure that the drain lines from the drain basins are completely
connected and properly terminated. A trap or seal of some type should be
incorporated in the line to prevent air bypass.
E. Check the water supply line to be sure water is available and that
the strainer, back flow preventer (by others) and detergent system are
properly installed and connected. Refer to piping diagram
fig 5.
F. Be sure that electrical power is available, that the wiring is
completed, and that the system blower is ready to energize. Refer to field
wiring diagram fig 6.
G. Be sure that all access doors are closed.
H. Close the system electrical supply switches, making power
available to the control and blower motor starter. Check to verify blower
rotation is as shown on the rotation indicator arrow.
I. Turn the “on-off” selector switch to the control “on”. The blower
should run (if installed) and the power supplies should be energized.
Electrical arc-over within the ionizing-collecting cells may occur. It is a
normal occurrence caused by accumulation dust from the constructions or
other sources in the cells and should soon subside. If the arc-over is
continuous and does not subside, recheck the routing of the high voltage
leads between the power supplies and the cells. Refer to field wiring
diagram fig 6. the ionizer lead must be connected to the ionizer and the
connector lead to the collector. If arc-over still occurs, or difficulty
other than that outlined above, refer to the trouble shooting reference
chart.
J. Be sure the detergent tank is clean, and then fill the tank 1/8
full with clean water. Do not fill with the detergent until start-up
adjustments have been completed.
K. (Review this paragraph in its entirety before initiating the wash
start button.)
Next, set the detergent volume setting per wash at the detergent feeder.
Manually initiate the wash cycle by pushing the wash start button on the
control. The wash control duration is 80 minutes and by means of a factory
preset programmable logic controller (PLC) will sequence the washing events
as previously outlined. When the detergent pump is energized, note the
amount that is used by observing the reduction in the liquid level in the
tank. The usage should be approximately 1 part of detergent and 20 parts of
water. The water and detergent requirements for each unit model are listed
in Table 1 on the piping schematic, fig 5. To adjust the volume output from
the pump, refer to the detergent system outline,
fig 4. The pump is a
constant displacement type and the amount of detergent forced into the water
supply to wash the unit is dependent upon the setting of the control valve
in the bypass return line to the reservoir. The side of the translucent
reservoir is marked with volume markers. Adjust the control valve to obtain
the correct usage for the given unit model, then secure the setting with the
Allen head set screw located in the valve adjustment knob. When the correct
adjustment has been made, remove the remaining water from the reservoir and
fill the tank with initial supply of detergent furnished.
L. When the wash control has cycled out, manually set the
programmable timer relay (TR), or initiator clock, located in the control
for automatic initiation of the washing operation. This setting can be
tailored to the washing frequency best suited for the specific application
and may be best explained by example.
Suppose the application of the equipment is to clean restaurant kitchen
exhaust air. The collected contaminant to be washed away is of greasy
nature, containing particulates such as smoke and fume from the grill, mist
and vapors from the French fryer, flour dust and other various matter that
is created by normal kitchen operation.
In our example, the restaurant operates Monday through Saturday (closed
Sunday) and opens daily at 6:00 am and closes daily at 11:30 pm. This busy
schedule presents a relatively heavy dirt loading and being of greasy nature
should be washed away daily. The best time being shortly after closing when
the atmosphere has settled but before the greasy contaminant collected has
had a chance to harden and set.
From the above, a wash schedule of everyday except Sunday at 1:00 am can be
established. As the duration of events preset at the factory is
approximately 80 minutes, the cycle will end at approximately 2:20 am.
Prior to setting the initiator clock it will be necessary to charge the
battery located inside the clock. This is accomplished by turning the
selector switch on the front of the control to the “on” position. A light
inside the switch will glow. If it does not glow, check to be sure there is
supply line power to the control. DO NOT PUSH THE WASH BUTTON. Allow the
control to remain in the “on” position for 24 to 36 hours while the battery
is charging.
To set the initiator clock, it is first necessary to set the existing time,
then the program times that are to be initiated.
To set existing time:
1. Depress the rest (R) button to cancel out any previous settings.
2. Slide the P-Run switch to the clock position. Monday (MO) will be
indicated.
3. Push the (1…7) button until the present day of the week is indicated.
4. Push the hour (h) button to the present hour of the day.
5. Push the minute (m) button to the minutes past the hour of the day.
6. Slide the P-Run switch to the run position. The colon will blink
indicating the clock has been set.
To set the programs (wash times) according to the times in the example
outlined above:
1. Slide the auto-manual switch to the auto position.
2. Slide the P-Run switch to the program (P) position. The word “on” and the
number 1 will appear on the display. This indicates the time the first
program is to be turned “on”.
3. Push the day (1…7) button until only the day Monday (MO) appears on the
display.
4. Push the hour (h) button until the designate hour (01:00) appears on the
display.
5. It is not necessary to set the minute (m), as 1:00 o’clock on the hour
was the selected wash initiation “on” time. The “on” time has now been set.
6. Next, set the program “off” time. This will be 1 minute after the “on”
time. A 1-minute duration is adequate program time, as the initiation signal
is sent to the wash control logic instantaneously.
7. Push the day (1…7) button until only the day Monday (MO) appears on the
display.
8. Push the hour (h) button until the hour 01:00 appears on the display.
9. Push the minute (m) button until the time 01:01 appears on the display.
Program 1, wash time “on” and “off” for Monday has now been set.
10. Next, set the second program which will be the Tuesday (TU) washing.
Push the program I/O (P) button. The word “on” and the number 2 will appear
on the display.
11. Repeat the setting process for TU as outlined above in steps 3 thru 9
for MO “on”-“off” time.
12. After the wash program has been set for TU, repeat the same setting
procedure for WE, TH, FR and SA. Omit SU.
13. Slide the P-Run switch to the run position. The existing time of day
will show on the display. The six selected washdays established in the
example have been set.
Note: using the above procedures, different washing day s and
“on-off” times may be established and set into the initiator clock to best
serve a specific application.
Notice: once the reset key (R) is pressed, the previous time and
program will be cleared to the initial state.
M. Kitchen Exhaust Applications
For safe and proper operation, adhere to the following instructions and
procedures:
1. Exhaust systems shall be operated during all periods of cooking in
restaurant applications.
2. Filter-equipped exhaust systems shall not be operated with filters
removed.
3. The posted instructions for manually operating the fire extinguishing
system shall be kept conspicuously posted in the kitchen and reviewed
periodically with employees by the management.
4. Listed exhaust hoods shall be operated in accordance with the terms of
their listings and the manufacture instructions.
5. Cooking equipment shall not be operated while its fire extinguishing
system or exhaust system is not operating or otherwise impaired.
3. Wash
Control and Detergent System Settings
Total time required for the complete wash cycle is
approximately 80 minutes. Four main events take place during the wash cycle
: wash, soak, rinse and dry. Once the wash control has been initiated,
either by manually pushing the washer start button, or through the means of
the automatic time clock, the wash events will take place automatically. The
time for each event has been preset at the factory in the programmable logic
control (PLC).
Some dirt is more tenacious than others to remove and may require a stronger
detergent solution. Average settings have been factory set. Best possible
settings for any given installation, however, are determined though
experience. Determination can be made by visually examining the collecting
elements after the first few washings.
To adjust the volume of detergent used within the given time setting, loosen
the knurled knob with an Allen wrench on the control valve located in the
by-pass line. Refer to the detergent system outline
fig 4. Turning knob
clockwise increases the volume and counter clockwise decreases the volume.
When adjustment has been made, be sure to retighten the setscrew.
4. Routine Maintenance
A. Washing Frequency
The frequency that the collected dirt is to be washed from the unit depends
upon the type and amount of dirt in the air to be cleaned. Dirt, which is
greasy in nature, tends to harden after collection and should be washed away
often. Likewise, units operating under extremely heavy dirt loads should be
washed more often as a large build-up of collected material will have a
tendency to “blow-off” if permitted to remain on the collecting elements for
long periods of time. In that the type and amount of dirt varies
geographically (and from one location to another in any given area) it is
recommended to start operation with a washing frequency of at least once a
week, for most applications except kitchen exhaust. Kitchen exhaust
applications should be washed daily. Schedules may then be altered as needed
after visual examinations of the collected material contained on the
ionizing collecting cells. Also, daily washing is not unusual for units
operating on heavy welding fume, kitchen exhaust hoods or similar
applications.
B. Detergent Effective washing is dependent upon detergent.
The detergent reservoir should be examined on a routine basis; a minimum
tank level established and never permitted to empty. An empty tank not only
means poor washing, but can also be detrimental to the pump. The inside of
the tank should be kept clean, free from dirt and foreign objects. The
detergent as supplied by Trion, Inc. is formulated specifically for
electronic air cleaners and SHOULD NOT be diluted when charging the tank. If
substitutes are used, they must be approved by Trion, so as not to void the
warranty and should be safe for use in ventilation systems and non –caustic,
as 95% of the ionizing collecting cells are constructed of aluminum and
special high voltage insulation and gasket seals.
The front panel of the control contains indicating lights for the power
supplies, one or two depending on the size of the ATS unit. The lights
should be observed on a daily basis to ensure that the electronic air
cleaners are operating.
5. Preventative Maintenance
A. Washing Frequency - As Required
The washing schedule and detergent reservoir level as outlined under routine
maintenance is again referenced here as excessively large contaminant
buildup on the collecting elements invites down time. Established routine
washing is a preventative maintenance requirement. The frequencies suggested
below should be altered if necessary.
B.
Fire control system – every 4 to 6 months or as required.
Inspection, cleaning and servicing of the fire extinguishing system and all
listed exhaust hoods shall be completed by properly trained and qualified
personnel. For a fire control system supplied with the ATS unit see
fig 7.
All actuation components, including remote manual pull stations, mechanical
or electrical devices, detectors, fire-actuated dampers, etc., shall be
checked for proper operation in accordance with the manufacturers listed
procedures. In addition to these requirements, the specific inspection
requirements of the applicable NFPA standards shall also be followed. If
required, certificates of inspection and maintenance shall be forwarded to
the authority having jurisdiction.
C. Grease removal devices and components – every 4 to 6 months.
Hoods, impingers, metal mesh filters, ionizing-collecting cells fan, ducts
and other appurtenances shall be cleaned to bare metal at frequent intervals
prior to surfaces becoming heavily contaminated with grease or oily sludge.
It may be advantageous to clean readily removable items, such as impingers,
metal mesh filters, ionizing collecting cells or other grease removal
devices in a soak tank, with a pressure hose or pressure cleaner. After
cleaning to the bare meta, components shall not be coated with powder, oils
or other substance.
When a cleaning service is used, a certificate showing date of inspection
and/ or cleaning should be maintained on the premises. Areas not cleaned
will be noted.
Flammable solvents or other flammable cleaning aids shall not be used.
At start of cleaning process, electrical switches that could be accidentally
activated shall be locked out. Components of the fire suppression system
shall not be rendered inoperable during the cleaning process.
Care shall be taken not to apply cleaning chemicals on fusible links or
other detection devices of the automatic extinguishing system.
When cleaning procedures are completed, all electrical switches and system
components shall be returned to an operable state. All access panels and/or
doors and cover plates shall be replaced. Dampers and diffusers shall be
positioned for proper air flow.
D. Water wash system – every 4 to 6 months
The water wash spray pattern should be checked on each nozzle to ensure that
a full spray pattern is developed. Distorted patterns are usually caused by
dirt in the nozzle orifice, which can be cleaned by inserting a small gauge,
soft copper wire into the orifice. If any one manifold contains several
nozzles that are restricted, the drain plug at the idler end of the manifold
should be removed, after the nozzles have been cleaned, and the manifold
flushed with clean water. The main supply line strainer and the strainer in
the detergent system should be checked and cleaned. Check the wash manifold
drive belt and linkage connections and replace or tighten as required.
|
WARNING! |
|
DO NOT USER HIGH
PRESSURE STEAM CLEANING EQUIPMENT TO CLEAN CELLS. THE EXCESSIVE
HEAT AND PRESSURE WIL CAUSE THE PLATES TO WARP AND IN TURN
POSSIBLY CAUSE EXCESSIVE ARCING. |
E. Power supplies and control – every 12 months
Examine the electrical components located inside the control housing for any
accumulated dirt or dust. If necessary, clean with a good brand of
electrical contact cleaner.
F. Blower bearings – every 4 to 6 months
Grease the two blower bearings at the grease fitting provided with Shell
Alvania #2, Texaco Multifac #2 or Mobilux #2. At this time, examine the
blower for any accumulated dirt and clean as required.
G. Motors – every 24 months
As the operation of detergent pump motor is limited, frequent oiling is not
required. Lubricate with several drops of SAE 10 motor oil every two years.
DO NOT OVER OIL. The manifold drive, detergent pump and blower motors have
sealed bearings, are factory lubricated for life and require no oiling.
6. Troubleshooting
|
WARNING! |
|
EXERCISE THE USUAL PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE. THE MAXIMUM
OPERATING OUTPUT FROM THE POWER SUPPLY IS 15, 000 VDC AND 5.5 MA to 11.0 MA
WHEN IN PARALLEL.
IF SAFETY SWITCHES ARE CLOSED AND CIRCUIT IS ENERGIZED, DO NOT TOUCH HIGH
VOLTAGE, WHEN THE CIRCUIT IS DE-ENERGIZED, ALWAYS BLEED OFF REMAININT STATIC
CHARGE WITH AN INSULATED HANDLED SCREW DRIVER BY SHORTING TO GROUND THE
POINTS OF HIGH VOLTAGE DC POTENTIAL. |
|
WARNING! |
|
RISK OF ELECTRIC SHOCK
The servicing instructions are for use by qualified personnel only. To
reduce the risk of electric shock, do not perform any servicing other than
that contained in the service instructions unless you are qualified to do
so. |
A. Introduction
This section on trouble shooting provides a description of potential
malfunctions, their cause, location and correction. A trouble reference
chart listing the most probable causes and corrections follows the general
text.
NOTE: All repair to the fire suppression system (if supplied) must be
completed by the authorized fire control contractor. For a system supplied
with ATS unit, refer to
fig 7.
The electronic air cleaner is the unit within the system that has the
highest efficiency collection rating and is also the one with the highest
potential for malfunction. When a malfunction does occur, the outage is
usually found in the electrical secondary circuit in the ionizing collecting
cells.
Indicating lights are installed in the face panel of the control to monitor
the electrical operation of each power supply and the ionizing collecting
cells they energize. The quantity of power supplies per unit is dependent
upon unit size with one supply to each ionizing collecting cell tier in
height. Other than the basic hand tools, it is advantageous to have a volt
meter with a 20 KVDC high voltage probe. These instruments are standard
catalog items by several manufactures.
B. Secondary Short Circuit
The most common outage is a short in the secondary circuit and is best
located through the process of elimination. Symptoms are a flickering
indicating light accompanied by an arcing noise in the ionizing collecting
cells or an indicating light that is not glowing.
A flickering light with an arcing noise is an indication of a high
resistance short circuit and a light that is not glowing is an indication of
a dead short. (A light that is not glowing can also be an indication of an
open circuit in the primary circuit. Refer to the paragraph on open
circuits.) The short may be in the power supply, the high voltage cables or
the ionizing collecting cells. To isolate the short to any one of these
three components, proceed as follows.
|
WARNING! |
|
When safety interlock devices are closed, do not come in contact with high
voltage components. The operating output from the high voltage power
supply-s is 12,500VDC and 6 mA.
When the power supply-s is de-energized there is a 20 second delay for the
voltage to decay. Always short from ground to a point of high voltage with a
well insulated jumper wire or an insulated handled screwdriver to bleed of
any remaining residual charge. |
1. Disconnect both high voltage leads from their respective
terminals in the power supply and support them away from any point of
contact
2. Energize the power supply:
a. If the light still flickers or does not glow; the trouble is indicated to
be in the power supply. First, replace the power supply on its entirety.
b. If the light glows steady with the leads disconnected the power supply is
indicated to be normal.
3. Next reconnect both high voltage leads to their respective terminals
inside the power supply and disconnect them at the ionizing collecting
cells. Support them away from any point of contact and energize the power
supply.
Note: It will be necessary to close the access door electrical
interlock switch operated by the access door and affix the junction box lid
with hardware supplied to close the electrical interlock switch on the box,
to complete the primary circuit to the power supply.
a. If either high voltage lead is defective, the light will
indicate the trouble. Each lead may then be checked separately by
disconnecting them one at a time from their respective terminals at the
power supply. When a lead is found to be defective, replace it in its
entirety. Do not repair or splice.
b. If the light glows steady with the leads disconnected at
the ionizing collecting cells, the trouble is then indicated to be in the
ionizing collecting cell. The trouble can then be isolated to the ionizer
section or collector cell section and then to an individual ionizer or
collector cell as follows:
1. First determine if the short
is in the ionizer section or the collecting section by connecting each high
voltage lead to its respective section, one at a time, and energizing the
power pack. (the lead not connected must be supported away from any point of
contact). The short symptoms will still exist for the section in which the
short is located. If the trouble causing the short is bridging both
sections, then the short will be indicated in both sections when they are
individually connected.
2. When the short is isolated
to either the ionizer or collector cell section, remove all the ionizers or
collectors cells in that section and visually check each for the following.
a) If the short is in the ionizer section look for a broken or defective
insulator or a broken ionizer wire
b) If the short is in the collector section look for a large piece of
foreign material bridging the collector plates or a defective insulator.
c) If the short is indicated to be in both sections, it will probably be a
foreign object bridging the air gap between the ionizer and the collector.
c. Open Circuits
Although open circuits can occur in the secondary, they usually take place
in the primary. If the unit contains only one power supply and the
indicating light does not glow, the outage is probably one of the following:
1. Supply line power to the control disconnected. Reconnect.
2. Open access door interlock in control of electronic air cleaner. Be sure
all access doors are properly closed and secured.
3. Outage in the power supply. Look for charred or burned components or a
loose wiring connection. Replace power supply or reconnect wiring.
4. Defective indicating light. Replace light.
d. Malfunctions other than short or open circuits. Refer to trouble
reference chart.
7. Spare Parts
Recommended spare part quantities are usually based on
the unit size and the amount of units per installation. For specific
recommendations, consult the Trion factory or nearest sales office.
Consideration, however, should be given to stocking the following
components:
| Description |
QTY |
|
Complete power supply |
1 |
|
Power supply indicating light
|
1 |
|
Ionizing-Collecting cell insulator
|
6 |
|
Trion detergent |
55 gal. |
Part
numbers are not listed as they are subject to change. Always state the unit
model and serial numbers when ordering parts.
See our entire
Line of Trion Products and
Commercial Kitchen Emissions Systems.
If you have
any questions, call us, we'll be glad to help!
1-877-688-2703
Contact
Us | About Us | View
Cart | Check
Out
©2001 - 2006 - BPA Air Quality Solutions
LLC
(DBA BreathePureAir.com) is for educational and research intentions only and
is not intended as an alternative for medical treatment or advice. Use of
this website, the 90 day return policy, and free shipping is subject to our
published
privacy policy,
terms of service,
and return policy.
|