Troubleshooting for ATS

Symptom Probable Cause Location Reason - Correction
Indicating Light Not Glowing Short Circuit Ionizing Section 1) Dirty insulator(s) - Clean

2) Defective insulator(s) - Replace

3) Foreign object between ionizing bar and ground electrode - remove

    Collecting Section of Cell 1) Dirty insulator(s) - Clean

2) Defective insulator(s) - Replace

3) Foreign material bridging plates - Remove

4) Bent plates - Straighten or Replace

    High Voltage Leads 1) Disconnected high voltage lead contacting ground - reconnect

2) Defective lead/insulation breakdown - Replace entire lead

    Power Supply Charred/overheated components - Replace power supply
Indicating Light Not Glowing Open Circuit Remote Mounted Control Box 1) Disconnected supply line power - reconnect

2) Faulty indicting light - replace

    Power Supply

1) Disconnected wire - replace

2)Charred/overheated components - replace power supply

    Electronic Air Cleaner Housing 1) Electrical interlock connector not closed - close access door and screw connectors together

2) Junction box wiring faulty - check and correct

3) Faulty electrical interlock connector - replace

Indicating Light Flickering High Resistance Short Circuit High voltage Circuit 1) Ionizer high voltage lead connected to collector section and collector lead to ionizer - reconnect leads

2) Loose or disconnect high voltage lead - tighten or reconnect

3) Loose or defective intercell connection (on multi-cell units) - tighten or replace

4) Foreign object adrift in ionizer or collector - remove

5) Dirty cells - remove, clean and replace

Loss In Capturing Velocity Restriction in Air Flow Modular Sections 1. Metal mesh filters dirty – clean

2. Bag filter saturated – replace
Loss in Collecting Efficiency Disconnected Components Electronic Air Cleaner 1. Disconnected high voltage lead – reconnect

2. Cell(s) in multicell unit not connected – repair or replace intercell high voltage connectors
Loss in Odor Control Decrease in Adsorption Ability Adsorber Module Saturated Activated Carbon – Replace with new or refurbished panels.

 


See our entire Line of Trion Products and Commercial Kitchen Emissions Systems.

If you have any questions, call us, we'll be glad to help!

1-877-688-2703

Contact Us  |  About Us  |  View Cart  |  Check Out
 

©2001 - 2006 - BPA Air Quality Solutions LLC
(DBA BreathePureAir.com) is for educational and research intentions only and is not intended as an alternative for medical treatment or advice. Use of this website, the 90 day return policy, and free shipping is subject to our published privacy policy, terms of service, and return policy.