|
OPERATION & SERVICE - FOR THE MAINTENANCE ENGINEER
also see
Troubleshooting for KES 2 & KES 4
|
WARNING! |
|
RISK OF ELECTRIC SHOCK
These service instructions are for
use by qualified personnel only. To reduce the risk of
electric shock, do not perform any servicing other than that
contained in the operating instructions unless you are qualified
to do so. |
1.
Introduction and Principle of Operation
The electronic air cleaner is technically known as an electrostatic
precipitator. In this type of equipment, all airborne particles, even of
microscopic size, are electrically charged (positively) as they pass through
a high voltage ionizer. Theses charged particles are then attracted and
adhere to a series of parallel collecting plates, which form the negative
elements of an electrostatic field.
The ionizer consists of charged Tungsten wire spaced between grounded
electrodes. The collecting section consists of parallel plates arranged so
that each alternate plate is charged while the intermediate plates are
electrically grounded.
Periodically, depending on the type and concentration of contamination in
the air, contaminate is washed from the plates by manually removing the
cells and cleaning them (item 4, a & b routine maintenance).
Two major functional components comprise the air cleaner:
(1) Ionizer and collecting cells to ionize and collect airborne particulate
matter
(2) Power supply-s to supply high voltage direct current to the
ionizing-collecting cells.
Normally, systems are designed for collection efficiencies in the range of
90% or more. Collecting a contaminate at these efficiencies, especially when
there are high concentrations, can result in large accumulations in a
relatively short period. Therefore, maintenance must encompass two areas:
the operation of the equipment for efficient collection, and the systematic
removal of the collected contaminate.
2. General Description
The ionizer-s & collecting cells (contaminate collecting elements) are
housed in the cabinet on slide rails. They can be removed from the cabinet
as required, through the access door, by sliding them out like drawers. Ionizer to ionizer and collector cell to collector cell electrical
connections are automatically made through spring plunger connectors. Power
supply-s on the ionizer/ collector cell access door make contact with
ionizer and collector cell spring plungers through an insulated high voltage
contact
IMPORTANT NOTE: Ionizer and collector cells are designed with a keyed slot
permitting one directional installation into the cabinet. When properly
installed, the brass contact plungers on the ionizer and cell should be
pointed toward the access door.
Installation of the perforated plate pre-filter and either a perforated
plate after-filter or metal mesh after-filter is required for all
installation of the pre/afterfilters, ionizer and collector cells, the
filter clip should be installed.
The power supply-s convert the 120/220 volt, 50/60HZ, single phase AC supply
to the high voltage DC needed to power the ionizing-collecting cells.
Potential of 12.5 13.0 kVDC are required for the ionizer sections and 6.0
6.5 kVDC for the collector sections of the cells.
3. Initial Start-up
A. Inspect the inside of the adjoining ductwork and KES cabinet to be sure
it is clean and free of any debris or construction materials. Ensure the
openings in the drain basin are free of any restrictions. The ducting, where
secured to the cabinet collars should be sealed liquid tight in accordance
with NFPA.
B. Inspect the ionizer and collecting cells to see that all of the ionizing
wires are intact, no large pieces of foreign material are lodged between the
plates, high voltage insulators are not cracked, and the ionizer and
collecting cells are properly installed in the cabinet.
C. Check the primary wiring to see that it is connected to the proper
terminal in both the KES junction box and the remote mounted control box.
(fig 3 and
fig 6).
D. Be sure the drain lines from the KES cabinet drain coupling are
completely connected and properly terminated. A trap or seal should be
incorporated in the line to prevent air bypass.
E. Be sure that electrical power is available, the wiring is completed, and
the system blower is ready to energize.
F. Be sure the flex cable connector (main power disconnect/ safety
interlock) is aligned, pushed down and screwed securely into the mating
flange mount connector on the access door. To help with alignment, marks
have been placed on the flex cable connector body and the flange mount
connector.
G. Close the system electrical supply switches, making power available to
the remote mounted control box and the system fan.
H. Turn the control box selector switch to the on position. The exhaust
fan should run (if installed) and the power supply-s should be energized.
Electrical arcing within the collecting cells may occur. It is a normal
occurrence caused by accumulation of dusts from construction or other
sources in the cell-s and should subside quickly. If the arcing is
continuous and does not subside, recheck the cell for trash, damaged plates
or cracked insulators.
IMPORTANT NOTE: Kitchen exhaust fan control and operation will vary with each installation.
The optional Trion remote mounted control box contains a 120/ 220 VAC relay
for connection to the exhaust fan starter coil. When the control box
selector switch is placed in the on position, the relay will energize the
fan starter coil.
For safe and proper Kitchen Exhaust operations, adhere to the following
instructions and procedures:
-
Exhaust systems shall be operated during all periods of cooking in
restaurant applications.
-
Filter-equipped exhaust systems shall not be operated with filters
removed.
-
The posted instructions for manually operating the fire extinguishing
system shall be kept conspicuously posted in the kitchen and reviewed
periodically with employees by the management.
-
Listed exhaust hoods shall be operated in accordance with the terms of
their listings and the manufacturer instructions.
-
Cooking equipment shall not be operated while its fire-extinguishing
system or exhaust system is not operating or otherwise impaired.
4. Routine Maintenance
A. Washing Frequency The frequency the collected dirty must be manually washed from the unit
depends upon the type and amount of dirt in the air to be cleaned. Dirt,
which is greasy in nature, tends to harden after collection and should be
washed away often. Likewise, units operating under extremely heavy dirt
loads should be washed more often as a large build-up of collected material
will have a tendency to blow off if permitted to remain on the collecting
elements for long periods of time. Trion recommends starting with a manual
washing frequency of at least once a week. This schedule may then be altered
as needed after visual examinations of the collected material contained on
the ionizing collecting cells. Daily manual washing is not unusual for units
operating on heavy kitchen exhaust hoods or similar contaminants.
Manual washing to clean the perforated plate prefilter, ionizer-s,
collecting cells, and metal mesh or perforated plate after-filters can be
performed in a soak tank, commercial carwash, or with a pressure hose or
pressure cleaner using a low pressure setting. Particular care should be
taken in cleaning each of the insulators.
|
WARNING! |
|
DO NOT USE HIGH PRESSURE STEAM CLEANING EQUIPMENT TO CLEAN CELLS. THE
EXCESSIVE HEAT AND PRESSURE WILL CAUSE THE PLATES TO WARP AND IN TURN
POSSIBLY CAUSE EXCESSIVE ARCING. |
|
WARNING! |
|
FLAMMABLE SOLVENTS OR OTHER FLAMMABLE CLEANING AIDS SHALL NOT BE USED. |
When a cleaning service is used, a certificate showing dates of inspection
and/ or cleaning shall be maintained on the premises.
B. Detergent Effective washing is dependent upon the detergent. The detergent as supplied
by Trion, Inc. is formulated specifically for electronic air cleaners. If
substitutes are used, Trion must approve them in order not to void the
warranty. Please contact Trion for this approval. Alternate detergents
should be safe for use in ventilation systems and non-caustic, as 95% of the
ionizer and collecting cells are constructed of aluminum and special high
voltage insulation and gasket seals.
C. Media filter and odor adsorption module replacement
(IF INSTALLED)
Every 3 to 6 Months Units equipped with this option may experience
different loading conditions and scheduled replacement may then be altered
as needed after visual examination.
D.
Electrical Operation
The KES and optional remote mounted control box both have LED indicating
lights to show power to the PWM power supply-s and output voltage present (
12.5 13.0 kVDC ionizer and 6.0-6.5 kVDC collector). Flickering or failed
LEDs indicate electrical arcing, electrical short and/or power failure.
5. Periodic Maintenance
A. Fire Suppression System (IF
INSTALLED) Every 6 Months Properly trained and qualified personnel shall complete inspection, cleaning
and servicing of the fire suppression system.
All actuation components, including remote manual pull stations, mechanical
or electrical devices, detectors, fire-actuated dampers, etc., shall be
checked for proper operation in accordance with the instructions in this
manual. In addition to these requirements, the specific inspection
5requirements of the applicable NFPA standard shall also be followed. If
required, certificates of inspection and maintenance shall be forwarded to
the authority having jurisdiction.
B. KES power supply enclosure
Every 12 Months The KES power supply enclosure located on the ionizer/ collector cell access
door should be examined for accumulated dirt and dust. If required, the
components should be cleaned using a good electrical contact cleaner. All
terminal connections should be checked for securement and tightened or
reworked as required.
|
WARNING! |
|
RISK OF ELECTRIC SHOCK
To reduce the risk of electrical shock, do not perform any servicing unless
all electrical power to the system has been turned off. |
At the start of the cleaning process, electrical switches that could be
accidentally activated shall be locked out. Components of the fire
suppression system (if installed) shall not be rendered inoperable during
the cleaning process.
|
CAUTION! |
|
Care should be taken not to apply
cleaning chemicals on any fusible links of other detection
devices of the automatic extinguishing system. |
6. Troubleshooting
|
WARNING! |
|
EXERCISE THE USUAL PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE. THE MAXIMUM
OPERATING OUTPUT FROM THE POWER SUPPLY IS 15, 000 VDC AND 5.5 MA to 11.0 MA
WHEN IN PARALLEL.
IF SAFETY SWITCHES ARE CLOSED AND CIRCUIT IS ENERGIZED, DO NOT TOUCH HIGH
VOLTAGE, WHEN THE CIRCUIT IS DE-ENERGIZED, ALWAYS BLEED OFF REMAININT STATIC
CHARGE WITH AN INSULATED HANDLED SCREW DRIVER BY SHORTING TO GROUND THE
POINTS OF HIGH VOLTAGE DC POTENTIAL. |
|
WARNING! |
|
RISK OF ELECTRIC SHOCK
The servicing instructions are for use by qualified personnel only. To
reduce the risk of electric shock, do not perform any servicing other than
that contained in the service instructions unless you are qualified to do
so. |
A. Introduction
This section on troubleshooting provides a description of potential
malfunctions, their cause, location and correction. A troubleshooting
reference chart listing the most probable causes and corrections follows the
general text.
IMPORTANT NOTE:
All repairs to the fire suppression system (if supplied)
must be completed by the authorized fire control contractor.
The
electronic air cleaner is the unit within the system that has the highest
efficiency collection rating. When a malfunction occurs, the outage is
usually found in the electrical secondary circuit in the ionizing/
collecting cell(s).
Indicating lights (LEDs) are installed in the face of the power supply
enclosure on the KES ionizer/ collector cell access door and provided with
the Trion optional remote mounted control box. These lights monitor the
electrical operation of each power supply and the ionizer-s and collecting
cell-s they energize. The KES-2 requires (1) power supply to energize (1)
ionizer and (2) collector cells. The 4000CFM KES-4 requires (2) power
supplies to energize (2) ionizers and (4) collector cells.
Other than the
basic hand tools, it is advantageous to have a volt meter with a 20 KVDC
high voltage probe.
B. Secondary Short Circuit The most common outage is a short in the secondary circuit, and is best
located through the process of elimination. Symptoms are a flickering
indicating light accompanied by an arcing noise in the ionizer-s and
collecting cell-s, or an indicating light that is not glowing. A flickering
light with an arcing noise is an indication of a high resistance short
circuit and a light that is not glowing is an indication of a dead short. (A
light that is not glowing can also be an indication of an open circuit in
the primary circuit. Refer to the paragraph on open circuits). The short may
be in the power supply, insulated high voltage contact on the access door,
ionizer-s or collecting cell-s. to isolate the short to any one of these
three components, proceed as follows:
|
WARNING! |
|
When safety interlock devices are closed, do not come in contact with high
voltage components. The operating output from the high voltage power
supply-s is 13,000VDC and 6 mA to 11.0 mA.
When the power supply-s is de-energized there is a 20 second delay for the
voltage to decay. Always short from ground to a point of high voltage with a
well insulated jumper wire or an insulated handled screwdriver to bleed of
any remaining residual charge. |
IMPORTANT NOTE: To perform this troubleshooting step, it will be necessary to close the
ionizer/ collector cell access door and re-connect the flex cable connector
to the flange-mounted connector on the access door. This will re-energize
the power supply-s. The panel on the ionizer/ collector cell access door
enclosure will also need to be removed.
-
Disconnect both high voltage leads from their respective terminals in the
power supply and support them away from any point of contact.
-
Energize the power supply:
-
If the light still flickers or does not glow the trouble is indicated to
be in the power supply. Replace the power supply in its entirety.
-
If the light glows steady with the leads disconnected, the power supply
is indicted to be normal.
-
Next reconnect both high voltage leads to their respective terminals
inside the power supply and disconnect them at the insulated door contacts
for the ionizer-s and collecting cell-s. Support them away from any point of
contact and energize the power supply.
-
If either high voltage lead is defective the light will indicate the
trouble. Each may then be checked separately by disconnecting them, one at a
time, from their respective terminals at the power supply. When a lead is
found to be defective, replace it in its entirety. Do not repair the splice
-
If the light glows steady with the leads disconnected from the insulated
door contact for the ionizer-s and collecting cell-s, the trouble is then
indicated to be in the ionizer and collecting cell. The trouble can then be
isolated to the ionizer section or collector cell section and then to an
individual ionizer or collector cell as follows:
-
First determine if the short is in the ionizer section or the collecting
section by connecting each high voltage lead to its respective section, one
at a time, and energizing the power pack. (the lead not connected must be
supported away from any point of contact). The short symptoms will still
exist for the section in which the short is located
-
When the short is isolated to either the ionizer or collector cell
section, remove all the ionizers or collectors cells in that section and
visually check each for the following.
-
If the short is in the ionizer section look for a broken or defective
insulator or a broken ionizer wire
-
If the short is in the collector section look for a large piece of
foreign material bridging the collector plates or a defective insulator.
C. Open Circuits Although open circuits can occur in the secondary, they usually take place
in the primary. If the unit contains only one power supply and the
indicating light does not glow, the outage is probably one of the following:
-
Supply line power to the power supply-s disconnected. Reconnect.
-
Main disconnect/ access door interlock on KES unscrewed. Close access
door and insert flex cable connector from junction box into flange mounted
connector on access door. Screw connectors together
-
Blown in-line fuse located on the power supply circuit board. Replace
power supply.
-
Outage in the power supply. Look for charred or burned components or a
loose wiring connection. Replace power supply or reconnect wiring.
-
Defective indicating light. Replace the light.
7. Spare Parts
Recommended spare part quantities are usually based on the unit size and the
amount of units per installation. For specific recommendations consult the
Trion factory or nearest sales office. Consideration however, should be
given to stocking the following components
| Description |
QTY |
|
PWM power supply |
1 |
|
Ionizer |
2 |
|
Collector cell |
4 |
|
Cell Insulators |
6 |
|
LED |
1 |
Part numbers are not listed as they are subject to change. Always state the
unit model and serial numbers when ordering parts.
See our entire
Line of Trion Products and
Commercial Kitchen Emissions Systems.
If you have
any questions, call us, we'll be glad to help!
1-877-688-2703
Contact
Us | About Us | View
Cart | Check
Out
©2001 - 2006 - BPA Air Quality Solutions
LLC
(DBA BreathePureAir.com) is for educational and research intentions only and
is not intended as an alternative for medical treatment or advice. Use of
this website, the 90 day return policy, and free shipping is subject to our
published
privacy policy,
terms of service,
and return policy.
|