|
Trion Air Boss Model 75 Info for
Installing Contractor
|
Model 75 Series Units with Integral Washing
System
for Model 75 Units With No Washing
System
1. Unpack and Inspect
At the time the unit is received, all shipping containers and their
contents should be examined for damage. Any damage occurring in shipment
must be immediately reported to the carrier, an inspection report completed
and a claim filed at the receiving point.
The unit cabinet is shipped completely assembled and, where size permits,
the ionizing-collecting cells are shipped inside the cabinet. On large
units, the upper tier of cells may be shipped in separate containers. The
controller, detergent feeder and other separate accessories are shipped in
the containers as noted on the packing list.
2. Position Air Cleaner Cabinet
To reduce weight for ease in handling, remove the pre-filters,
after-filters and the ionizing-collecting cells from the cabinet, and place
them safely aside. Position the cabinet in the designated location giving
consideration to the following points:
-
Provide sufficient clearance in front of the
access doors for ionizing-collecting cell and mechanical filter removal.
A minimum of 39 inches is required. (see
figure 5)
-
Level the cabinet to assure proper drainage
from the drain pan.
-
Unless specific design features have been
prearranged, the direction of airflow through the cabinet may be either
from the right or the left. When the ionizing-collecting cells are
reinstalled, the directional arrows on the cell end plates must concur
with airflow through the cabinet. If mist suppressors have been
specified, they are to be installed on the air entering side of the
unit.
After the cabinet has been properly located, it
may be secured into place at the predrilled factory mounting pads either by
bolting or welding.
3. Connect Adjoining Ductwork
Depending on the application, the installation plan may or may not call
for adjoining ductwork on the air entering and/or air leaving sides of the
cabinet.
When adjoining ducting is to be installed, the bottom of the horizontal duct
runs should be relatively flat and sloped toward the cabinet drain pan for
an 18-inch length. As a result, any wash water splash back occurring during
the washing operation will run back into the drain pan.
Duct securement to the collar may be completed using the predrilled flange.
The seam should be made air and watertight by caulking or gasketing.
When a blower is installed downstream from the Trion cabinet, the ducting
between the cabinet and the blower will be under negative pressure and
should be made air tight to prevent infiltration of contaminated air.
After the ductwork has been installed, clear remaining material or debris
from inside ducts and bottom of cabinet, then re-install both the mechanical
filters and the ionizing-collecting cells.
|
NOTE: Follow the directional
arrows located on the cell end plates. The side of each cell
containing the spiked ionizer blades must be located on the air
entering side of the cabinet. The brass contact plungers on the
cell should be inserted toward the back of cabinet. Also, mist
suppressors, when specified, must be located on the air entering
side of the cabinet. |
4. Mount Detergent System
Refer to Detergent Outline Drawing (Figure 9). The detergent system
should be located as close to the unit as practical, but should not exceed
20 feet in elevation difference. Service space must be provided for periodic
manual filling of the detergent tank and to gain access to the pump and
motor assembly. When positioned, the assembly may be secured in place at the
predrilled factory mounting pads, either by bolting or welding.
5. Connect Drain
Connect a drain line to the pipe coupling provided in the cabinet drain
basin in accordance with the governing plumbing codes. The drain line must
be sealed with a trap or other means to prevent air by pass. If a trap is
used, it should hold sufficient water column to overcome the system air
pressure and to assure that loss of liquid from evaporation between cleaning
periods will not break the seal. The drain line should not be smaller than
the drainpipe coupling, or it will otherwise restrict the flow of water.
Elevation of the equipment may be required to allow adequate draining.
6. Connect Water Wash Supply
The items furnished to be included in the wash water supply are a
strainer, an electrically operated solenoid valve, and a detergent system.
Refer to the Piping Schematic (Figure 10).
Unless otherwise specified, the water wash supply should be hot (140°F
recommended-WATER HEATER NOT SUPPLIED BY TRION) at the volume specified
for the given unit, and at a full flow pressure between 40 and 60 PSIG.
|
WARNING! |
|
Adequate precautions should be
taken in the event the water supply, detergent system and drains
are subjected to freezing temperatures. |
Although not required, a pressure gage and a
manual service valve are recommended as shown in the diagram. The components
should be located within the system to provide for service access.
7. Mount Controller
The Controller should be mounted at eye level and located as close to
the air cleaner as practical. It must be mounted indoors out of the weather
unless supplied with a weatherproof cabinet. Allow sufficient space in front
of the access door(s) for service. Refer to appropriate Control/Remote PWM
Box Outline Drawing for mounting hole layout and dimensions.
8. Complete Wiring
(a). High Voltage Wiring
|
WARNING! |
|
EXERCISE ALL THE NORMAL
PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE AND COMPLY WITH NEC
AND ALL APPROPRIATE LOCAL CODES. |
The high voltage wiring entails
interconnecting the power supply(s) to the ionizing-collecting cell(s)
through the factory-installed junction box on top of the cabinet. All
the wiring in the cabinet has been completed at the factory.
Refer to the Field Wiring Diagram. Two high voltage leads, Red/Black
Tracer for the ionizer and one Red for the collector, are factory
furnished. Each lead is to be run in separate conduit and must be of
continuous run (do not splice) between the controller and the
ionizing-collecting cell terminal connection in the junction box.
(b). Primary Wiring
The Wash Controller is the main distribution
point for all primary wiring. The various electrical components involved
are connected to and powered from the controller. These interlocks are
safety switches that prevent access to the charged high voltage
components without first turning “OFF” the high voltage by interrupting
the 24 VDC input to the PLC. Refer to the appropriate Field Wiring
Diagram.
(c). Grounding
An earth ground must be provided to the
Model
75 cabinet and control. All ground connections
must be in contact with bare metal and securely
affixed. Ground conductor size and connection
means will be in accordance with all applicable
electrical code standards.
9. Check Out for System Start-up
When the installation has been completed, assure that the equipment is
ready for start-up by checking the following:
-
All construction debris is removed from the
ionizing-collecting cells, drain basin and ductwork.
-
The inside of the controller and detergent
tank are clear of any foreign materials.
-
The drain line from the Trion drain basin is
clear and completely connected to its point of termination.
-
All piping is completed to the manifold
headers and wash water is available.
-
Supply line power is available and
electrical wiring is completed to the following components:
-
Controller
-
Solenoid Valve
-
Detergent Pump Motors
-
Manifold Drive Motors
-
Electrical Interlocks
-
Ionizing-Collecting Cells
-
The System Fan
|
NOTE: Do not put the initial
supply of detergent into the detergent tank. This is to be done
after volume settings are made at start-up. |
|
|
Model 75 Units With No Washing
System
|
|
1. Unpack and Inspect
At the time the unit is received, all shipping containers and their
contents should be examined for damage. Any damage occurring in shipment
must be immediately reported to the carrier, an inspection report completed
and a claim filed at the receiving point.
The unit cabinet is shipped completely assembled and, where size permits,
the ionizing-collecting cells are shipped inside the cabinet. On large
units, the upper tier of cells may be shipped in separate containers. The
controller, detergent feeder and other separate accessories are shipped in
the containers as noted on the packing list.
2. Position Air Cleaner Cabinet
To reduce weight for ease in handling, remove the pre-filters,
after-filters and the ionizing-collecting cells from the cabinet, and place
them safely aside. Position the cabinet in the designated location giving
consideration to the following points:
-
Provide sufficient clearance in front of the
access doors for ionizing-collecting cell and mechanical filter removal.
A minimum of 39 inches is required. (see
figure 5)
-
Level the cabinet to assure proper drainage
from the drain pan.
-
Unless specific design features have been
prearranged, the direction of airflow through the cabinet may be either
from the right or the left. When the ionizing-collecting cells are
reinstalled, the directional arrows on the cell end plates must concur
with airflow through the cabinet. If mist suppressors have been
specified, they are to be installed on the air entering side of the
unit.
After the cabinet has been properly located, it
may be secured into place at the predrilled factory mounting pads either by
bolting or welding.
3. Connect Adjoining Ductwork
Depending on the application, the installation plan may or may not call
for adjoining ductwork on the air entering and/or air leaving sides of the
cabinet.
When adjoining ducting is to be installed, the bottom of the horizontal duct
runs should be relatively flat and sloped toward the cabinet drain pan for
an 18-inch length.
Duct securement to the collar may be completed using the predrilled flange.
The seam should be made air and watertight by caulking or gasketing.
When a blower is installed downstream from the Trion cabinet, the ducting
between the cabinet and the blower will be under negative pressure and
should be made air tight to prevent infiltration of contaminated air.
After the ductwork has been installed, clear remaining material or debris
from inside ducts and bottom of cabinet, and then re-install both the
mechanical filters and the ionizing-collecting cells.
|
NOTE: Follow the directional
arrows located on the cell end plates. The side of each cell
containing the spiked ionizer blades must be located on the air
entering side of the cabinet. The brass contact plungers on the
cell should be inserted toward the back of cabinet. Also, mist
suppressors, when specified, must be located on the air entering
side of the cabinet. |
4. Connect Drain
Connect a drain line to the pipe coupling provided in the cabinet drain
basin in accordance with the governing plumbing codes. The drain line must
be sealed with a trap or other means to prevent air by pass. If a trap is
used, it should hold sufficient water column to overcome the system air
pressure and to assure that loss of liquid from evaporation between cleaning
periods will not break the seal. The drain line should not be smaller than
the drainpipe coupling.
5. Mount Controller
The Controller should be mounted at eye level and located as close to
the air cleaner as practical. It must be mounted indoors out of the weather
unless supplied with a weatherproof cabinet. Allow sufficient space in front
of the access door(s) for service. Refer to appropriate Control/Remote PWM
Box Outline Drawing for mounting hole layout and dimensions.
6. Complete Wiring
(a). High Voltage Wiring
|
WARNING! |
|
EXERCISE ALL THE NORMAL
PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE AND COMPLY WITH NEC
AND ALL APPROPRIATE LOCAL CODES. |
The high voltage wiring entails
interconnecting the power supply(s) to the ionizing-collecting cell(s)
through the factory-installed junction box on top of the cabinet. All
the wiring in the cabinet has been completed at the factory.
Refer to the Field Wiring Diagram. Two high voltage leads, Red/Black
Tracer for the ionizer and one Red for the collector, are factory
furnished. Each lead is to be run in separate conduit and must be of
continuous run (do not splice) between the controller and the
ionizing-collecting cell terminal connection in the junction box.
(b). Primary Wiring
The Controller is the main distribution
point for all primary wiring. The various electrical components involved
are connected to and powered from the controller. These interlocks are
safety switches that prevent access to the charged high voltage
components without first turning “OFF” the high voltage by interrupting
the 24 VDC input to the PLC. Refer to the appropriate Field Wiring
Diagram.
(c). Grounding
An earth ground must be provided to the
Model 75 cabinet and control. All ground connections must be in contact
with bare metal and securely affixed. Ground conductor size and
connection means will be in accordance with all applicable electrical
code standards.
7.
Check Out for System Start-up
When the installation has been completed, assure that the equipment is
ready for start-up by checking the following:
-
All construction debris is removed from the
ionizing-collecting cells, drain basin and ductwork.
-
The drain line from the Trion drain basin is
clear and completely connected to its point of termination.
-
Supply line power is available and
electrical wiring is completed to the following components:
-
Controller
-
Electrical Interlocks
-
Ionizing-Collecting Cells
-
The System Fan
See our entire
Line of Trion Products and
Commercial Kitchen Emissions Systems.
If you have
any questions, call us, we'll be glad to help!
1-877-688-2703
Contact
Us | About Us | View
Cart | Check
Out
©2001 - 2006 - BPA Air Quality Solutions
LLC
(DBA BreathePureAir.com) is for educational and research intentions only and
is not intended as an alternative for medical treatment or advice. Use of
this website, the 90 day return policy, and free shipping is subject to our
published
privacy policy,
terms of service,
and return policy.
|
|