Owners Manual
INSTALLATION – READ THOROUGHLY
-
Carefully unpack unit from shipping crate or
carton and examine for damage in shipment.
-
Remove ionizer/collector cell(s),
pre-filters and after-filters.
-
Attach 500 pound (227 kg) test chain to the
ceiling joist using:
-
Wood joist – 3/8” (m10) eye bolts
-
Metal joist – wrap chain around joist at
least twice and secure with 500 pound (227 kg) test connecting link
-
Chain should be cut to allow the unit to
hang from a predetermined height from the floor. (Usually 10-12 feet or
3.0-3.6 m).
-
The unit is equipped with a locator dimple
in each corner on the top and bottom. Using the dimples as a guide,
drill (4) 13/32” dia. (10.3 mm) holes that will be required for mounting
the eyebolts, which are attached to the suspension chain.
-
Position a 3/8” (m10) diameter eyebolt (or
larger) in each hole and secure with a washer and appropriate nuts.
NOTE: Be sure to place two nuts on each eyebolt to act a locking
nut. Failure to do so may cause the nuts to loosen and the unit to fall.
-
Using 3/8” (10 mm) connecting links, attach
unit to chain. Use turnbuckles on diagonally opposite chains.
NOTE: Foul threads on turnbuckles after leveling unit to ensure
that the turnbuckle will not "“back off" or loosen and cause the unit to
fall.
-
The units can be suspended with the
direction of airflow from the right to left. If a left to right airflow
is desired, the unit may be flipped over and the eyehooks installed in
what was originally the bottom.
LIQUID AEROSOL APPLICATION
INSTALLATIONS
The unit is equipped with a sump, drain hole sized to accept a
½” NPT fitting.
For the collection of liquid contaminant:
-
Install drain fitting to allow for the attachment of a liquid collection
cup or drain hose. A drain fitting is available from your representative. An
“S” trap is required in the drain hose to ensure proper drainage of the
collected liquid.
-
Raise the front corner of the unit, opposite of the drain corner, ½” (13
mm) to enable the collected liquid to flow to the drain sump.
Contaminants to be collected – such as oils in
vaporous state – must be condensed into particulate form prior to entering
the ionizing-collecting cells in order to maintain the anticipated
efficiency. Gases, vapors or any nonparticulate cannot be precipitated and
will therefore pass through the air cleaner. Any condensing that takes place
downstream from the air cleaner defeats the purpose. Similarly, heavy
concentrations of water vapor, or other matter that becomes highly
conductive when condensed, must be prevented from entering and/or condensing
in the collecting elements to prevent electrical arc over and shorting.
ELECTRICAL INSTALLATION
All units must be wired directly in the junction box on the
access door side of the unit. Use NEC Class I wiring methods. Size branch
circuit protection in accordance with the NEC. Refer to the appropriate
enclosed wiring diagram in the attached figures.
|
WARNING |
| EXERCISE ALL THE NORMAL
PRECAUTIONS WHEN WORKING WITH HIGH VOLTAGE AND COMPLY WITH NEC
AND ALL APPROPRIATE LOCAL CODES. |
Check Out for System Start-up
When the installation has been completed, assure that the equipment is
ready for start-up by checking the following:
-
All construction debris is removed from the
ionizing/collecting
cells, drain connections and ductwork.
-
The drain line from the Trion drain basin is
clear and
completely connected to its point of termination.
-
Supply line power is available and
electrical wiring
is completed to the junction box.
See the full
Trion AirBoss T-Series line of
industrial electronic air cleaners.
See our entire
line of
Smoke Eaters,
Ambient Air Cleaners,
Mist
Eliminators,
Fume
Extractors or all
Industrial Air Purifiers.
If you have
any questions, call us, we'll be glad to help!
1-877-688-2703
Contact
Us | About Us
©2001 - 2006 - BPA Air Quality Solutions
LLC
(DBA BreathePureAir.com) is for educational and research intentions only and
is not intended as an alternative for medical treatment or advice. Use of
this website, the 90 day return policy, and free shipping is subject to our
published
privacy policy,
terms of service,
and return policy.
|